| Application | The combined gas control system with DKJ-02 carbon monoxide (CO) and hydrogen (H₂) gas detectors and US-12 central controller is designed for continuous monitoring of toxic and highly flammable gas concentrations in rooms where combustion processes take place, hydrogen technologies or energy storage solutions are used. The system operates using a reliable 4–20 mA signal, ensuring stable data transmission and easy integration into industrial and building management systems. The DKJ-02 CO detector continuously measures the concentration of carbon monoxide in the air and protects people from invisible, odorless, but extremely dangerous effects on health. The DKJ-02 H₂ detector is designed for early detection of hydrogen leaks – H₂ is a very light and fast-dispersing but extremely explosive gas, so a quick response is critical. The US-12 central controller receives signals from both detectors, analyzes them, and displays them on the screen in real time. When the set alarm limits are exceeded, the controller activates audible and visual signals and relay outputs that can be used to control ventilation systems, shut off hydrogen or fuel supply, transmit emergency signals, or integrate with other systems. This combined system is a reliable solution for boiler rooms, industrial facilities, hydrogen storage or production facilities, laboratories, energy storage systems, and technical areas where it is necessary to ensure human safety from the effects of CO and effective prevention of hydrogen leaks and explosions. The system uses carbon monoxide (CO) and NO₂ (nitrogen dioxide) gas detectors and a US-12 central controller for continuous monitoring of toxic combustion gases in rooms where internal combustion engines, burners, or other thermal equipment are in operation. The system uses a reliable 4–20 mA signal, ensuring stable data transmission and easy integration into automatic safety and building management systems. DKJ-02 CO and NO₂ detectors continuously measure the concentration of hazardous gases in the air and transmit a proportional 4–20 mA signal to the central controller. The CO detector protects against invisible and odorless carbon monoxide, which poses a direct threat to human health, while the NO₂ detector is designed for early detection of nitrogen dioxide, a gas that irritates and damages the respiratory tract. The US-12 central controller receives signals from two detectors, analyzes them, and displays them on the screen in real time. When the set alarm limits are exceeded, the controller activates audible and visual signals and relay outputs that can be used to control ventilation systems, transmit warning signals, or integrate with other systems. This combined system is a reliable solution for underground car parks, garages, tunnels, boiler rooms, industrial and technical premises where effective protection against the effects of CO and NO₂ on human health is required and a safe and normative air quality level is ensured. Service pole up to 150m2 |
| DKJ-02 CO gas detector | Detectable gases: carbon monoxide (CO) Measurement principle: electrochemical Measurement range: 0–300 ppm (other ranges available on request) Output signal: 4–20 mA (proportional to CO concentration) Supply voltage: 12–24 V DC Power consumption: ≤ 2 W Measurement accuracy: ±5 % F.S. Response time (T90): < 30 s Operating temperature: –20 °C … +50 °C Ambient humidity: up to 95 % RH (non-condensing) Housing material: aluminum Protection class: IP67 Mounting height: in the breathing zone (approx. 1.5 m above the floor) Mounting: wall-mounted |
| DKJ-02 H2 gas detector | Detectable gases: hydrogen (H₂) Measurement principle: catalytic (for combustible gases) Measurement range: 0–50% LEL Output signal: 4–20 mA (proportional to H₂ concentration) Supply voltage: 12–24 V DC Power consumption: ≤ 3 W Measurement accuracy: ±3 % F.S. Response time (T90): < 30 s Operating temperature: –20 °C … +50 °C Ambient humidity: up to 95 % RH (non-condensing) Housing material: aluminum Protection class: IP67 Mounting height: ceiling (H₂ gas is lighter than air) Mounting type: wall or bracket |
| US-12 control panel 4-20mA | • Number of channels: 2 • Supported sensors: CO, LPG, CH₄, etc. (with 4–20 mA output) • Power supply: AC 100–260 V, 50/60 Hz • Display: digital (concentration and status display) • Alarm levels: AL1 / AL2 • Signaling: audible and visual • Relay outputs: 4 relays (NO / NC) • Housing type: plastic, wall-mounted • Protection class: IP40 • Operating temperature: 0 °C … +40 °C • Mounting: wall-mounted |
| Warranty | 24 mėn |
Siekdami užtikrinti geriausią patirtį, naudojame tokias technologijas kaip slapukai, kad išsaugotume ir (arba) gautume prieigą prie įrenginio informacijos. Sutikdami su šiomis technologijomis galėsime apdoroti tokius duomenis kaip naršymo elgsena ar unikalūs ID šioje svetainėje. Nesutikimas arba sutikimo atšaukimas gali turėti neigiamos įtakos tam tikroms funkcijoms ir savybėms.